Re: laser cooling

From: Philip Marder (marder@iquest.net)
Date: Thu May 14 1998 - 09:17:27 EST


Kent,
I believe that most of the lasers we are talking about here have flow rate
and/or pressure sensors for the laser cooling water.  Decreasing the flow
rate might not be the answer.

Phil Marder

On Wed, 13 May 1998, Kent Cavender-Bares wrote:

> 
> Hi All,
> 
>         I may not be thinking about this correctly, but it seems to me that
> when using a heat exchanger system (like the LaserPure) connected to a
> building chilled water system, that "over-cooling" leading to condensation
> should be somewhat easy to cure.  Since the chilled water does not pass
> directly through the laser, it is the flowrate of chilled water of a given
> temperature which will determine the temperature of the water circulating to
> the laser (for a given chilled water temperature, and a given heat
> exchanger).  If one can monitor the temperature of the incoming chilled
> water, it should be possible to adjust the flow of the chilled water to meet
> the cooling needs of the laser(s).  That is, in summer (when chilled water
> systems are typically cooler) the chilled water valve could be opened less
> than in the winter.  This could be a problem if the heat exchanger requires
> a minimum flowrate of chilled water, then the option with a mixing valve as
> presented earlier today seems like the way to go.  Also, the more complex
> solution would be advisable if a fail-safe system is required in a lab with
> multiple users.  Warm or cold, though, these things sure are loud!  A good
> wrapping in insulation makes it more bearable if it must stay in the flow lab...
> 
> Hope this helps someone,
> Kent
> 
> 


This archive was generated by hypermail 2.1.6 : Thu Jan 01 2004 - 17:35:18 EST